Energy measurement device hot/cold for high flow rates with threaded fitting and data transmission

Composition
 
Type
Multiple-jet counter with magnetic transmission.
Electronic unit technical data
Temperature range: 1 - 150 °C - Temperature difference in heating phase: 3 - 100 K - Temperature difference in cooling phase: -3 - -50 K - Storage temperature: 0 - 55 °C - Minimum temperature difference in heating phase: 0.05 K - Minimum temperature difference in cooling phase: -0.05 K - Temperature measurement resolution: 0.01 °C - Measurement frequency: every 30 seconds
Impulses: 10 litres/impulse - Display: LCD with 8 digits + special characters - Energy measurement unit: MWh - Power supply: battery 3.6 V lithium, estimated maximum battery life 6+1 years, not guaranteed, M-Bus (if the instrument is connect to an M-Bus network) - Data storage EEPROM / daily - Reading data: settable - Protection class: IP65 - Electromagnetic class: E1 - Mechanical class: M1 - Temperature probes: Pt500, Ø 5 mm (for measurement DN25), Ø 6 mm (for measurement DN32 and DN40), cable length: 3 m
Dimensions (Length x Width x Height): 198 x 123,7 x 45,8 mm
Communication via M-bus protocol in compliance with standard UNI EN 1434.
Use "Kit USB optical head" to set the primary address of the measuring device.
Energy measurement device for high flow rates is confirm to MID 2004/22/CE.