Commercial on/off Air-Water heat pump EH 3310÷6510 with axial fans and water-circulation unit

Composition
 
Working range
Outdoor air temperature: -5 - 40 °C (Heating), -10 - 42 °C (Cooling)
Exchanger outlet water temperature: 42 - 52 °C, air >6 °C (Heating), 4 - 20 °C (Cooling)
Max exchanger inlet water temperature: 47 °C (Heating), 25 °C (Cooling)
Temperature drop on the evaporator: 3 - 8 °C.
Water pressure: minimum 0,5 Barg - maximum 3 Barg.

Loading...

Notes
 
APPLICATION AT LOW TEMPERATURE ACCORDING THE REGULATIONS EU N° 811-813/2013
Seasonal space heating energy efficiency class: A+
Sound power: dB(A) 78 (mod. 3310 2CI), 79 (mod. 3810 2CI), 80 (mod. 4510 - 5010 2CI), 81 (mod. 6010 - 6510 2CI)


Refrigerant R410A. Power supply (V-ph-Hz): 400-3+N-50.

Data referred to the application with terminal air units and to the following conditions:
Cooling: water 12/7 °C and outdoor temperature 35 °C.
Heating: water 40/45 °C and outdoor temperature 7° C d.b.
(*) Without electric pump.